Knightfly, your post is confusing me!

Started by Michael Jones on 30 November 2003. 5 replies.

Originally posted at johnlsayers.com, topic 1042.

And a view from the other side: Notice that the staggered stud, exterior wall has no studs that touch the flanking interior wall.
Image not preserved: mockup2.JPG
Hey Mike, I'd reverse your wall materials layouts making sure you seal those ends with acoustical sealant (the opposing wall materials.) Bryan Giles
Michael, good catch - I originally started out to draw that WITHOUT the left, wood framed wall - the horizontal 2x4 was just going to be an anchor for the rubber-surrounded sway brace that holds the right, steel stud frame in place without hard contact. In my drawing, though, this is showing a CEILING with two walls coming up to it. Still, there is a flanking path thru the solid wood wall frame's cap and into the ceiling joists. I'll re-do that as soon as I can, thank you - Your proposed layout is fine as far as framing goes, but you'll get better corners if you bring one panel in from the left, leave 1/4" gap, caulk, then one panel in from the right, 1/4" gap, caulk, and alternate til you're done - this gives more caulk beads and a much more tortuous path for sound leaks, without any hard contact between intersecting wall panels. I'll notate that drawing that confused you, until I can replace it with a better one. Again, thanks for catching that... Steve
Point taken guys. I just threw the material up there for the photo. The actual method of installation will be like you're saying.
Michael, I redrew the drawing in question - see what you think... Steve